Water testing at Liberte House (FOI)

Water testing at Liberte House (FOI)

Produced by the Freedom of Information office
Authored by Government of Jersey and published on 30 September 2019.
Prepared internally, no external costs.

Request

A

The reason why the water was tested at Liberte House, La Motte street

B

Date of the first tests carried out and the results of the first water test in particular the level of Legionella species found

C

Date of any further tests carried out and the results of any further tests that were carried out

Response

A

The water was tested at Liberte House when it was found that the standard flushing regime had not been carried out for the 4th floor of the building while it was not in use.

B

Samples were taken from two outlets on the 4th floor on 18 July 2019. The results are shown in the following table:

4th floor sample results

​Sample location

​Result

​4th Floor outlet 1​13,040 cfu legionella species per 0.5 litre
​4th Floor outlet 2​8,720 cfu legionella species per 0.5 litre

 

C

The water system was disinfected on 3 August 2019 with a water management and flushing programme implemented the week commencing the 5 August.

The tests were expanded to cover every floor with a total of 44 samples being taken. Six outlets were found to have legionella species. The results are shown in the table below.

Please note that the levels found, whilst elevated, were still designated as safe.

​Sample results ​

​Sample Location

​Results

Ground floor (GF) kitchen​20 cfu legionella species per litre
​GF Disabled toilet basin​20 cfu legionella species per litre
​1st floor kitchen​20 cfu legionella species per litre
​1st floor disabled shower​140 cfu legionella species per litre
​2nd floor disabled basin​60 cfu legionella species per litre
​4th floor kitchen1​20 cfu legionella species per litre